AR Series
 

 
  AR heaters are now considered the generic radiant tube heater within the market place. They offer an outstanding reputation for combining efficiency, economy and low noise operation. They are ideal for heating factories, warehouses and workshops - indeed any industrial or commercial premises whether old or new that requires effective, efficient heating with low running costs.


The AR range has an advanced slim burner assembly that incorporates two compartments. One houses the combustion chamber with a specially constructed air flow passage and burner head to eliminate combustion air turbulence and flame roar. The other contains the twin gas safety shut off valve and airflow proving switch that monitors the differential air pressure within the burner for enhanced safety of the heater.

The AR range is available in 'U'-tube, linear, double linear and herringbone manifold configurations.
Ambi-Rad gas fired AR heaters are manufactured from the finest materials including stainless steel reflectors, end caps, turbulators and guarded air inlet cover. Emitter tubes are CALCOAT® (heat treated aluminised steel) or stainless steel depending on the model.





AR SERIES - Benefits

  Reduces running costs. Savings of between 25-60% of fuel costs can be achieved
  Provides even heat coverage at low level
  Does not directly heat the air - ideal in areas of high air infiltration
  Minimises roof heat losses - reduced stratification
  Systems can be controlled easily to provide varying zoned temperatures and operating times
  Provides rapid heating up times
  Easy to install and maintain


APPLICATIONS

  Factories
  Foundries
  Engineering Workshops
  Warehouses
  Retail Outlets
  Aircraft Hangars
  Vehicle Distribution Centres
  Vehicle Workshops
  Glasshouses
  Sport Arenas
  Museums


SYSTEM DESIGN

The AR series offers the consultant the widest range of burner inputs possible in designing the heating requirements of any industrial or commercial building.

However, it is recommended as a good practice that the large kW burners are not mounted at low level and particular care is taken to ensure adequate heat coverage is provided when specifying these higher rated burners.


TECHNICAL DATA

 
 
MODEL AR13* AR22 AR35 AR40 AR45 AR50
NOMINAL HEAT INPUT kW MIN 9.75
(Nat. Gas Only)
16.6
(Nat. Gas Only)
28.0
(Nat. Gas Only)
- - -
  kW MAX 13.0 22.0 35.0 40.0 45.0 50.0
NOMINAL GAS RATE PER BURNER
NATURAL GAS MIN 0.9m³/h 1.60m³/h 2.60m³/h - - -
  MAX 1.21m³/h 2.06m³/h 3.28m³/h 3.73m³/h 4.20m³/h 4.76m³/h
(LPG) PROPANE MIN - - - - - -
  MAX 0.5m³/h 0.83m³/h 1.44m³/h 1.55m³/h 1.74m³/h 1.93m³/h
GAS SUPPLY GAS SUPPLY CONNECTION R ½ ½ in BSP EXTERNAL THREAD : MAX PRESSURE 25mbar (min 16.5mbar) Nat.Gas 55mbar Propane (min 37mbar)
ELECTRICAL SUPPLY 230 VOLT 1 PHASE 50 Hz
CURRENT RATING 0.55 AMP MAX. (INDUCTIVE)
EXTERNAL FUSE RATING 3 AMP EXTERNAL
IGNITION ELECTRONIC PROGRAMME START UP WITH SPARK IGNITION
DIMENSIONAL DATA
OVERALL LENGTH m 'U' 3.47 5.24 5.89 5.89 7.62 7.62
  SL 6.63 8.02 12.62 12.62 15.2 18.2
  DL 13.26 15.80 25.00/30.00 25.00/30.00 - -
OVERALL WIDTH mm 'U' 435 490 666 666 666 666
  SL/HB 235 460 460 460 460 460
  DL 235 460 460 460 - -
EXHAUST FLUE (dia). TWIN WALL 'U'
SL
DL
All Exhaust Flue 125mm (5in)
TOTAL INSTALLED WEIGHT kg 'U' 51 63 95 95 144 144
  SL 56 72 117/140 117/140 130/156 130/156
  DL 112 145 234/281 234/281 - -

N.B. Special lengths are available. Contact Ambi-Rad design office for details.

† Note: DL heaters only rated at maximum input. For building air supply and ventilation requirements please refer to BS6896:1991 Installation of gas fired overhead radiant heaters for industrial and commercial heating.

MOUNTING HEIGHTS
MODEL MOUNTING
POSITION
MINIMUM
MOUNTING HEIGHT
RECOMMENDED
MOUNTING HEIGHT RANGE
WHEN MOUNTING OVER THESE HEIGHTS
CONTACT AMBI-RAD DESIGN OFFICE
AR13 HORIZONTAL 3.00 3.30-4.20 over 4.2
AR13 INCLINED/WALL MOUNTED 2.70 3.00-4.00
AR22 HORIZONTAL 3.60 4.80-7.00 over 7.00
AR22 INCLINED/WALL MOUNTED 3.00 4.20-4.90
AR35 HORIZONTAL 4.30 4.90-11.00 over 11.00
AR35 INCLINED/WALL MOUNTED 3.60 4.00-7.00
AR40 HORIZONTAL 4.30 4.90-11.00 over 11.00
AR40 INCLINED/WALL MOUNTED 3.60 4.00-7.00
AR45 HORIZONTAL 5.00 5.90-12.00 over 12.00
AR45 INCLINED/WALL MOUNTED 4.30 5.00-8.00
AR50 HORIZONTAL 5.70 6.90-13.00 over 13.00
AR50 INCLINED/WALL MOUNTED 5.00 6.00-9.00


CLEARANCE DISTANCES TO COMBUSTIBLE MATERIALS
MODEL AR13 AR22 AR35 AR40 AR45 AR50
ABOVE REFLECTOR 150 150 150 150 150 150
ABOVE BURNER FAN ASSEMBLY FLUED 500 500 500 500 500 500
BENEATH TUBES 1250 1250 1500 2100 2100 2100
TO THE SIDES FLUED 600 600 600 600 600 600
FROM FAN OUTLET UNFLUED 1200 1200 1200 1200 1200 1200

All distances are in millimetres