| CENTURION
- Gas Fired Unit Heaters CENTURION UF
The Ambi-Rad Centurion range is a
new generation of gas-fired air heating products.
Designed to enhance energy efficiency, provide simple low
cost installation and to facilitate ease of maintenance.
The units offer considerable benefits at the most
competitive cost.
| |
|
Lower running
costs |
|
| |
|
high efficiency |
| |
|
high airflow for minimal
stratification |
| |
|
Lower installed
costs |
|
| |
|
lightweight, simple four
point suspension |
| |
|
reduces the requirements
for destratification |
| |
|
Ease of
maintenance |
|
| |
|
drop-down burner access |
| |
|
proven reliability of
components |
The patented, new low resistance heat exchanger allows
more than 20% additional airflow without any increase in
fan speed or electrical consumption.
CENTURION UFE
The Centurion UFE provides additional Fuel
Economy by incorporating an integral powered flue and
automatic spark ignition as standard features. The power
vented flue eliminates the unnecessary loss of heated air
that is associated with open flues, thus providing
significant energy savings.
This combination of energy
saving features, and reduced installation costs,
generally allows the additional costs of the higher
specification units to be recovered within the initial
year of operation.
Furthermore, roof
penetrations can be avoided as the rear flue outlet on
the Centurion UFE allows the use of a simple through the
wall terminal.
ENERGY SAVING FEATURES
| |
|
ENHANCED
EFFICIENCY: |
| |
|
Lower running
costs |
| |
|
LONGER AIR
THROWS: |
| |
|
Improved
Distribution |
| |
|
HIGH AIRFLOW: |
| |
|
Reduced
stratification |
STANDARD FEATURES
| |
|
Suitable for
natural gas |
| |
|
Aluminised steel
heat exchanger |
| |
|
Horizontal
louvres |
| |
|
Dual limit
switches |
| |
|
UF only - Piezo ignition |
UFE UNITS ONLY
| |
|
Auto spark
ignition |
| |
|
Fan assisted flue |
OPTIONAL FEATURES
FACTORY FITTED
| |
|
Unit suitable for
propane gas |
| |
|
Air recirculation
thermostat |
OPTIONAL ITEMS FOR ON
SITE FITTING
| |
|
Downturn nozzles
(30° & 60°) |
| |
|
Power flue
venters (UF only) |
| |
|
Vertical louvres |
TECHNICAL DATA
| MODEL |
50 |
75 |
100 |
125 |
165 |
200 |
250 |
300 |
400 |
| NOMINAL
OUTPUT |
kW |
11.7 |
17.6 |
23.4 |
29.3 |
38.7 |
46.9 |
58.6 |
70.3 |
93.8 |
| |
Btu/h |
40000 |
60000 |
80000 |
100000 |
132000 |
160000 |
200000 |
240000 |
320000 |
| GAS
RATE |
m³/h |
1.38 |
2.06 |
2.75 |
3.44 |
4.54 |
5.5 |
6.87 |
8.25 |
11 |
| |
ft³/h |
48.5 |
72.8 |
97.1 |
121.4 |
160.2 |
194.2 |
242.7 |
291.3 |
388.3 |
| GAS CONNECTION |
|
BSP
in |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
| NOMINAL FLUE
DIA. |
UF |
mm |
100 |
125 |
150 |
175 |
200 |
200 |
250 |
250 |
250 |
| |
UFE |
mm |
100 |
100 |
100 |
125 |
125 |
125 |
215 |
150 |
150 |
| MAX. FLUE
LENGTH |
(UFE) |
m |
12 |
12 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
| AIRFLOW |
m³/h |
1145 |
1886 |
2516 |
3272 |
4151 |
5033 |
6293 |
7589 |
10066 |
| |
ft³/min |
673 |
1111 |
1481 |
1926 |
2444 |
2963 |
3704 |
4444 |
5926 |
| MOTOR RATING |
UF |
kW |
0.10 |
0.11 |
0.22 |
0.24 |
0.27 |
0.29 |
0.35 |
0.45 |
0.58 |
| |
UFE |
kW |
0.15 |
0.17 |
0.28 |
0.31 |
0.34 |
0.37 |
0.43 |
0.53 |
0.67 |
| RUNNING AMPS |
UF |
|
0.45 |
0.50 |
1.00 |
1.05 |
1.10 |
1.20 |
1.80 |
2.00 |
2.50 |
| |
UFE |
|
0.75 |
0.80 |
1.30 |
1.35 |
1.40 |
1.60 |
2.20 |
2.40 |
2.90 |
| MOUNTING
HEIGHT* |
m |
2.3-2.7 |
2.3-2.7 |
2.3-2.7 |
2.5-3.0 |
2.5-3.0 |
2.5-3.0 |
2.5-3.5 |
3.0-4.0 |
3.0-5.0 |
| THROW |
m |
10 |
13 |
17 |
21 |
25 |
26 |
29 |
32 |
38 |
| APPROX.
WEIGHT (NET) |
kg |
36 |
40 |
44 |
58 |
68 |
77 |
93 |
100 |
125 |
CLEARANCE DATA
| TOP |
BOTTOM |
SIDES |
REAR |
FRONT OF
DRAUGHT HOOD |
FLUE |
| 152mm |
610mm |
460mm |
610mm |
Models
25/125-1830.
Models 165/250-2440
Models 300/400-3050 |
152mm |
Maximum
inlet pressure 30 mbar. Minimum inlet pressure 17.5 mbar.
* Use lower mounting height unless a downturn
nozzle is fitted. Throw depends on height of building,
mounting height of heater, room temperature and louvre
setting.
Reduce flue length by 3m for each
90° bend.
DIMENSION DATA
DIMENSIONS
| MODELS |
50 |
75 |
100 |
125 |
165 |
200 |
250 |
300 |
400 |
| A |
..WIDTH |
344 |
395 |
446 |
592 |
516 |
592 |
732 |
732 |
941 |
| B |
..HEIGHT |
737 |
737 |
737 |
737 |
990 |
990 |
990 |
990 |
990 |
| C |
..SUSPENSION POINTS |
367 |
367 |
367 |
367 |
495 |
495 |
495 |
495 |
495 |
| D |
..FLUE DIAMETER (INTERNAL) |
102 |
127 |
153 |
178 |
203 |
203 |
254 |
254 |
254 |
| E |
..FRONT TO FLUE CENTRE |
451 |
451 |
451 |
436 |
543 |
543 |
543 |
543 |
543 |
| F |
..CABINET LENGTH |
687 |
687 |
687 |
687 |
802 |
802 |
802 |
802 |
802 |
| G |
..VENTER OUTLET DIAMETER (UFE) |
102 |
102 |
102 |
127 |
127 |
127 |
127 |
152 |
152 |
| H |
..OVERALL LENGTH |
687 |
687 |
794 |
794 |
911 |
911 |
937 |
937 |
937 |
| J |
..15° OUTLET |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
0 |
180 |
| K |
..INLET LOCATION |
261 |
267 |
328 |
366 |
363 |
366 |
314 |
314 |
330 |
| L |
..FRONT TO BRACKET CENTRE |
148 |
148 |
148 |
148 |
124 |
124 |
124 |
124 |
124 |
|