| NOR-RAY-VAC
Continuous Radiant Tube Heating System
NOR-RAY-VAC 'LR'
SYSTEM - Features
The Nor-Ray-Vac 'LR' system is a
lightweight gas fired continuous radiant tube heating
system that offers the widest range of burner inputs of
any continuous radiant system and comprises the following
features:
| |
|
In-line fuel
efficient burners (input between 12-46kW) |
| |
|
Common vacuum fan
operation |
| |
|
Stoichiometric or
'perfect' combustion |
| |
|
92% combustion
efficiency |
| |
|
Good visual
appearance
The Nor-Ray-Vac system is designed to provide uniform
heat coverage over the entire floor area.
Alternatively the system can also cater for distinct zones
providing a varied degree of comfort level within the
overall layout of the building.
|
SYSTEM OPERATION
The system operates on a vacuum principle and utilises a zero governor within a dedicated gas valve
ensuring optimum efficiency, reliability and safety.
The zero governor will only allow flow of gas when a vacuum is created by the fan. Therefore apart
from the standard failsafe (where the gas valve locks out with ignition or gas supply failure), the zero
governor also mechanically prevents gas flow in the event of vacuum shut down. The control of gas
flow through the zero governor and the air flow into the mixing chamber under the influence of the
vacuum fan, also enables stoichiometric combustion at the burner head.
The stoichiometric principle, where gas and air are mixed in the correct proportions so that secondary
air is not required to complete combustion of the gas, permits the inclusion of further burners within
the same tubing, ‘downstream’ of the first burner, ensuring evenly distributed heat along the length
of radiant tube.
In order to conform to the latest European Gas Appliance regulations (EN 777) an end vent module
burner has been developed to ‘prove’ the flow of air at the start of each radiant branch. The end vent
module burner is a feature which is unique to the Nor-Ray-Vac ‘LR’ series, and instils the principle
of ‘safety of operation’ as a prerequisite of design.
NOR-RAY-VAC 'LR' SYSTEM
- Benefits
| |
|
Low running
costs. Saving between 25-60% of fuel cost can be
achieved |
| |
|
Qualifies for inclusion on the government’s energy technology listing |
| |
|
Good aesthetic
integration with building |
| |
|
Minimal flue
penetration - single flue system. Up to 550kW per
single discharge |
| |
|
Capable of
running three 46kW burners in a radiant branch |
| |
|
Widest range of
burner inputs for any continuous system |
| |
|
Uniform even
distribution of heat |
| |
|
Reliability and
safety of operation to the latest European
Standard for multi-burner systems (pr EN777) |
| |
|
Rapid response to change |
Applications for the
lightweight Nor-Ray-Vac 'LR' system are varied and
may include:
| |
|
Garages and
Showrooms |
| |
|
Sports Halls |
| |
|
Superstore Retail
Outlets |
| |
|
Vehicle
Distribution Centres |
| |
|
New Low Energy
Factories |
| |
|
Aircraft Hangars |
| |
|
Museums |
| |
|
Glasshouses |
| |
|
Warehouses |
Burner control housing
Chassis style with detachable pivoting lid
for ease of access during maintenance.
Reflectors
The radiant tube sections of the system
are fitted with reflectors made of Aludip
or stainless steel to direct infra-red rays
downward. The reflectors are a unique
design profile to maximise the reflected
radiant heat, minimise convective loss
and maximise rigidity.
System tube
Calcoat radiant tube, hot coated internally
and externally with aluminium, then
heat treated fusing the aluminium into
the surface of the steel, ensuring the
seam weld is coated with aluminium.
The tube and fittings are connected
together using special stainless steel
wrap-round couplings.
End vent, module/burner
At the start of each radiant branch an
EVM is connected to the rear of the first
combustion chamber. The EVM/burner
incorporates a vacuum pressure switch
to prove flow at the start of the radiant
branch to comply with European gas
appliance standards.
Vacuum fans
Cast aluminium or robust steel plate
fabricated centrifugal fan coated with
heat and corrosion resistant paint.
Capable of static minimum pressure of
29 mbar at 20°C. (45 mbar for BH300.)
Burner head assembly
A lightweight aluminium construction,
with a ceramic burner head insert.
The aerodynamic shape reduces pressure
drop across the burner head and promotes
a greater volume flame at the bottom
of the tube where maximum release
heat is desirable.
Control panel
A range of control panels specially
designed for Nor-Ray-Vac radiant
heating systems are available.
TECHNICAL DATA
| BURNER MODEL |
NRV12LR |
NRV18LR |
NRV24LR |
NRV32LR |
NRV38LR |
NRV46LR |
| INPUT RATING kW |
| Gross |
12 |
18 |
24 |
32 |
38 |
46 |
| GAS CONSUMPTION |
| Nat.Gas G20 m³/h |
1.143 |
1.715 |
2.287 |
3.05 |
3.62 |
4.38 |
| Propane G31
m³/h |
0.452 |
0.677 |
0.903 |
1.21 |
1.43 |
1.73 |
| INLET GAS PRESSURE mbar |
| Max. |
50 |
50 |
50 |
50 |
50 |
50 |
| Min. |
12 |
12 |
12 |
12 |
12 |
12 |
| RADIANT TUBE LENGTH (DIST.
BETWEEN BURNERS) m |
| Min. |
5.2 |
7.4 |
9.4 |
14 |
18 |
23 |
| Max. |
7.2 |
10.2 |
13.1 |
18 |
23 |
27 |
| MAX. TUBE TEMPERATURE °C |
| |
450 |
450 |
450 |
480 |
480 |
480 |
| BURNER MODEL |
NRV12LR |
NRV18LR |
NRV24LR |
NRV32LR |
NRV38LR |
NRV46LR |
| ELECTRICAL DETAILS |
| Volts |
230 |
230 |
230 |
230 |
230 |
230 |
| PH |
1 |
1 |
1 |
1 |
1 |
1 |
| Amps |
0.05 |
0.05 |
0.05 |
0.05 |
0.05 |
0.05 |
| Hz |
50 |
50 |
50 |
50 |
50 |
50 |
| NOISE RATING AT 3m BELOW BURNER |
| db(A) |
46 |
47 |
47 |
48 |
50 |
51 |
| NR+2 |
40 |
41 |
41 |
42 |
44 |
45 |
| BURNER MODEL |
NRV12LR |
NRV18LR |
NRV24LR |
NRV32LR |
NRV38LR |
NRV46LR |
| DISTANCE FROM COMBUSTIBLES mm |
| Below
Tube |
END-VENT/IN-LINE |
Without
Undershield |
1120/1250 |
1120/1250 |
1120/1250 |
1400/1700 |
1570/2100 |
1700/2100 |
With
Undershield |
760/850 |
760/850 |
760/850 |
760/850 |
785/1050 |
850/1050 |
| Above Tube |
250 |
250 |
250 |
250 |
250 |
250 |
| Horizontally |
Standard
Reflector |
600/770 |
600/770 |
600/770 |
700/850 |
700/1000 |
700/1000 |
Perimeter
Reflector |
305/450 |
305/450 |
305/450 |
305/510 |
305/600 |
305/600 |
| MIN. MOUNTING HEIGHT m |
| |
3 |
3.6 |
4 |
4.7 |
5.3 |
6 |
| WEIGHT BURNER kg |
| |
10 |
10 |
10 |
10 |
10 |
10 |
known as ARC in the USA
İAmbi-Rad Limited 2000.
|