  NOR-RAY-VAC Continuous Radiant Tube Heating System

NOR-RAY-VAC 'LR' SYSTEM - Features

The Nor-Ray-Vac 'LR' system is a lightweight gas fired continuous radiant tube heating system that offers the widest range of burner inputs of any continuous radiant system and comprises the following features:

  In-line fuel efficient burners (input between 12-46kW)
  Common vacuum fan operation
  Stoichiometric or 'perfect' combustion
  92% combustion efficiency
 

Good visual appearance

The Nor-Ray-Vac system is designed to provide uniform heat coverage over the entire floor area.

Alternatively the system can also cater for distinct zones providing a varied degree of comfort level within the overall layout of the building.

 

SYSTEM OPERATION

The system operates on a vacuum principle and utilises a zero governor within a dedicated gas valve ensuring optimum efficiency, reliability and safety. The zero governor will only allow flow of gas when a vacuum is created by the fan. Therefore apart from the standard failsafe (where the gas valve locks out with ignition or gas supply failure), the zero governor also mechanically prevents gas flow in the event of vacuum shut down. The control of gas flow through the zero governor and the air flow into the mixing chamber under the influence of the vacuum fan, also enables stoichiometric combustion at the burner head.

The stoichiometric principle, where gas and air are mixed in the correct proportions so that secondary air is not required to complete combustion of the gas, permits the inclusion of further burners within the same tubing, ‘downstream’ of the first burner, ensuring evenly distributed heat along the length of radiant tube.

In order to conform to the latest European Gas Appliance regulations (EN 777) an end vent module burner has been developed to ‘prove’ the flow of air at the start of each radiant branch. The end vent module burner is a feature which is unique to the Nor-Ray-Vac ‘LR’ series, and instils the principle of ‘safety of operation’ as a prerequisite of design.

NOR-RAY-VAC 'LR' SYSTEM - Benefits

  Low running costs. Saving between 25-60% of fuel cost can be achieved
  Qualifies for inclusion on the government’s energy technology listing
  Good aesthetic integration with building
  Minimal flue penetration - single flue system. Up to 550kW per single discharge
  Capable of running three 46kW burners in a radiant branch
  Widest range of burner inputs for any continuous system
  Uniform even distribution of heat
  Reliability and safety of operation to the latest European Standard for multi-burner systems (pr EN777)
  Rapid response to change

Applications for the lightweight Nor-Ray-Vac 'LR' system are varied and may include:

  Garages and Showrooms
  Sports Halls
  Superstore Retail Outlets
  Vehicle Distribution Centres
  New Low Energy Factories
  Aircraft Hangars
  Museums
  Glasshouses
  Warehouses

 

Burner control housing
Chassis style with detachable pivoting lid for ease of access during maintenance.

Reflectors
The radiant tube sections of the system are fitted with reflectors made of Aludip or stainless steel to direct infra-red rays downward. The reflectors are a unique design profile to maximise the reflected radiant heat, minimise convective loss and maximise rigidity.

System tube
Calcoat radiant tube, hot coated internally and externally with aluminium, then heat treated fusing the aluminium into the surface of the steel, ensuring the seam weld is coated with aluminium. The tube and fittings are connected together using special stainless steel wrap-round couplings.

End vent, module/burner
At the start of each radiant branch an EVM is connected to the rear of the first combustion chamber. The EVM/burner incorporates a vacuum pressure switch to prove flow at the start of the radiant branch to comply with European gas appliance standards.

Vacuum fans
Cast aluminium or robust steel plate fabricated centrifugal fan coated with heat and corrosion resistant paint. Capable of static minimum pressure of 29 mbar at 20°C. (45 mbar for BH300.)

Burner head assembly
A lightweight aluminium construction, with a ceramic burner head insert. The aerodynamic shape reduces pressure drop across the burner head and promotes a greater volume flame at the bottom of the tube where maximum release heat is desirable.

Control panel
A range of control panels specially designed for Nor-Ray-Vac radiant heating systems are available
.




TECHNICAL DATA

BURNER MODEL NRV12LR NRV18LR NRV24LR NRV32LR NRV38LR NRV46LR
INPUT RATING kW
Gross 12 18 24 32 38 46
GAS CONSUMPTION
Nat.Gas G20 m³/h 1.143 1.715 2.287 3.05 3.62 4.38
Propane G31 m³/h 0.452 0.677 0.903 1.21 1.43 1.73
INLET GAS PRESSURE mbar
Max. 50 50 50 50 50 50
Min. 12 12 12 12 12 12
RADIANT TUBE LENGTH (DIST. BETWEEN BURNERS) m
Min. 5.2 7.4 9.4 14 18 23
Max. 7.2 10.2 13.1 18 23 27
MAX. TUBE TEMPERATURE °C
  450 450 450 480 480 480


BURNER MODEL NRV12LR NRV18LR NRV24LR NRV32LR NRV38LR NRV46LR
ELECTRICAL DETAILS
Volts 230 230 230 230 230 230
PH 1 1 1 1 1 1
Amps 0.05 0.05 0.05 0.05 0.05 0.05
Hz 50 50 50 50 50 50
NOISE RATING AT 3m BELOW BURNER
db(A) 46 47 47 48 50 51
NR+2 40 41 41 42 44 45


BURNER MODEL NRV12LR NRV18LR NRV24LR NRV32LR NRV38LR NRV46LR
DISTANCE FROM COMBUSTIBLES mm
Below Tube END-VENT/IN-LINE
Without
Undershield
1120/1250 1120/1250 1120/1250 1400/1700 1570/2100 1700/2100
With
Undershield
760/850 760/850 760/850 760/850 785/1050 850/1050
Above Tube 250 250 250 250 250 250
Horizontally
Standard
Reflector
600/770 600/770 600/770 700/850 700/1000 700/1000
Perimeter
Reflector
305/450 305/450 305/450 305/510 305/600 305/600
MIN. MOUNTING HEIGHT m
  3 3.6 4 4.7 5.3 6
WEIGHT BURNER kg
  10 10 10 10 10 10

known as ARC in the USA