EnviroAir
 
 
  SPECIFICATION 'ST' SERIES

Cabinets
All components exposed to products of combustion are manufactured from aluminised steel. Exterior panels have a durable epoxy powder coat finish.

Heat Exchanger
The Thermocore venturi tube heat exchanger assembly is manufactured from special grade aluminised steel. For applications using fresh air or where the temperature rise across the unit is less than 22
oC, optional stainless steel (AISI 409) heat exchangers are recommended. For areas where chlorinated vapours may be present, corrosion resistant stainless steel (AISI 316) should be specified.

Burners
Corrosion resistant aluminised steel burners with stainless steel ribbons are mounted in a slide-out burner tray. The burner tray withdraws from the left side of the unit (when facing the air discharge), opposite hand units are available as an option.

Gas and Safety Controls
A multi functional gas control valve and a fully automatic ignition system provide full safety monitoring of the heater operation. Fan operation is controlled by an integral fan control which delays start up until the unit has reached operating temperature and continues to operate the fan after the burners have shut off, until all useful heat has been dissipated into the building. A differential pressure switch monitors the operation of the integral power flue venter, so that in the event of a flue or combustion air blockage or failure of the venter fan, the unit would not operate.

A limit switch thermostat shuts down the heater in the event of overheating. For additional safety a dual limit thermostat is fitted on all EnviroAir units.

Air Handling
STA fan models are fitted with direct drive axial flow fans and single phase 230V motors. STA units are supplied complete with horizontal louvres.

STB and STE centrifugal fan models are fitted with double inlet, centrifugal blowers, and a belt drive with an adjustable motor pulley to allow small on-site adjustments to be made. Standard units are fitted with single phase 230V motors, optional three phase motors are available for increased duty.

STB and STE are supplied as standard with a duct outlet spigot for connection to ductwork. The data table indicates the airflow and static pressure available for ducted applications with the standard motor. For higher airflows or for static pressures up to 400 pascals, larger motors may be specified. The data table indicates the maximum airflows, excluding filter and damper resistance.

TECHNICAL DATA


100 125 150 175 225 300 400
NOMINAL HEAT OUTPUT kW 23 28 34 40 50 69 91
GAS RATE G20 Natural Gas m³/h 2.75 3.36 4.07 4.76 6.03 8.25 11.01
GAS CONNECTION BSP in ¾ ¾ ¾ ¾ ¾ ¾ ¾
FLUE DIAMETER mm 100 100 100 130 130 130 130
COMBUSTION AIR INLET mm 100 100 100 130 130 130 130
AXIAL FAN MODELS STA
AIRFLOW FREEBLOWING m³/h 1700 2400 3700 3700 4200 5600 7900
MOTOR RATING kW 0.075 0.12 0.12 0.12 0.12 2 x 0.12 2 x 0.12
MOUNTING HEIGHT m 2.5 2.5-3.0 2.5-3.0 2.5-3.25 2.5-3.5 2.5-3.5 2.5-40
THROW * m 17 20 28 28 28 32 38
WALL OPENING mm 140 140 140 185 185 185 185
ROOF OPENING mm 150 150 150 200 200 200 200
CENTRIFUGAL FAN MODELS STB & STE
AIRFLOW FREEBLOWING m³/h 2200 2600 3600 4150 5000 6800 8600
MOUNTING HEIGHT m 3.0 3.0 3.0-3.5 3.0-3.5 3.0-4.0 3.0-4.5 3.0-5.0
THROW * m 24 25 30 31 32 34 47
MOUNTING HEIGHT c/w 90° m - - 3.0-6.0 3.0-6.0 3.5-7.0 4.0-4.5 4.0-10.0
STANDARD MOTOR kW 0.18 0.18 0.37 0.37 0.55 0.75 0.75
AIRFLOW DUCTED (Standard Motor) m³/h 1900 2100 3000 3500 4200 5800 7300
MAXIMUM PRESSURE  (Standard Motor) kW 100 100 150 100 100 100 100
MAXIMUM MOTOR SIZE kW 1.1 1.1 1.5 1.5 2.2 3.0 3.0
MAXIMUM AIRFLOW m³/h 3000 4000 5000 5000 7200 9000 12,000
MAXIMUM PRESSURE AT MAXIMUM AIRFLOW Pa 400 400 400 400 150 400 200
MAXIMUM AIRFLOW AT 400Pa m³/h 3000 4000 5000 5000 6400 9000 11,000

* Throw depends on height of building, mounting height of heater, room temperature and louvre settings

 


  ©Ambi-Rad Limited 2000.