'T'
SERIES DIMENSIONAL DATA
DIMENSIONS TA & TB (mm)
| |
|
75 |
100 |
125 |
150/175 |
200/225 |
250 |
300 |
350 |
400 |
| Heater Width |
A |
488 |
488 |
558 |
698 |
838 |
1048 |
1048 |
1187 |
1328 |
| Height |
B |
819 |
819 |
819 |
819 |
895 |
895 |
895 |
895 |
895 |
| Depth axial fan model TA |
C |
865 |
865 |
908 |
927 |
929 |
921 |
921 |
929 |
929 |
| Depth centrifugal fan model
TB |
D |
1133 |
1133 |
1133 |
1226 |
1226 |
1133 |
1133 |
1226 |
1226 |
| Suspension centres TA &
TB |
E |
348 |
348 |
418 |
558 |
698 |
908 |
908 |
1048 |
1187 |
| Duct outlet internal width TB |
F |
317 |
317 |
387 |
527 |
667 |
876 |
876 |
1016 |
1156 |
| Flue outlet diameter |
G |
125 |
150 |
175 |
200 |
200 |
200 |
250 |
250 |
250 |
| Front to centre of flue TA
& TB |
H |
489 |
489 |
489 |
489 |
438 |
438 |
438 |
438 |
438 |
| Side clearance (controls
access) * |
J |
640 |
640 |
710 |
850 |
990 |
1200 |
1200 |
1340 |
1480 |
| Side clearance (non control
side) |
|
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
| Top clearance |
|
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
| Bottom clearance (to
combustibles) ** |
|
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
| Minimum flue height (m) |
|
2.0 |
2.0 |
2.0 |
2.0 |
2.0 |
2.5 |
2.0 |
2.5 |
2.5 |
| Approx weight TA (kg) |
|
80 |
80 |
86 |
93 |
118 |
146 |
146 |
166 |
191 |
| Approx weight TB (kg) |
|
98 |
98 |
118 |
136 |
147 |
177 |
177 |
185 |
223 |
* Units may be ordered with right hand controls, i.e. controls
access, flue and air inlet on right-hand side (non standard).
** Units
may be base mounted on a suitable non-combustible surface.
DIMENSIONS TE (mm)
| |
|
75 |
100 |
125 |
150/175 |
200/225 |
250 |
300 |
350 |
400 |
| Heater Width |
A |
488 |
488 |
558 |
698 |
838 |
1048 |
1048 |
1187 |
1328 |
| Height |
B |
819 |
819 |
819 |
819 |
895 |
895 |
895 |
895 |
895 |
| Ducted air inlet width TE |
C |
451 |
451 |
451 |
591 |
730 |
940 |
940 |
1080 |
1219 |
| Ducted air inlet height TE
(open cabinet) |
D |
706 |
706 |
706 |
706 |
783 |
783 |
783 |
783 |
783 |
| Suspension centres TE |
E |
348 |
348 |
418 |
558 |
698 |
908 |
908 |
1048 |
1187 |
| Duct outlet internal width TE |
F |
317 |
317 |
387 |
527 |
667 |
876 |
876 |
1016 |
1156 |
| Flue outlet diameter |
G |
125 |
150 |
175 |
200 |
200 |
200 |
250 |
250 |
250 |
| Front to centre of flue TE |
H |
489 |
489 |
489 |
489 |
438 |
438 |
438 |
438 |
438 |
| Side clearance (controls
access) * |
J |
640 |
640 |
710 |
850 |
990 |
1200 |
1200 |
1340 |
1480 |
| Side clearance (non control
side) |
|
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
| Top clearance |
|
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
| Bottom clearance (to
combustibles) ** |
|
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
152 |
| Minimum flue height (m) |
|
2.0 |
2.0 |
2.0 |
2.0 |
2.0 |
2.5 |
2.0 |
2.5 |
2.5 |
| Approx weight TE (kg) |
|
106 |
106 |
134 |
151 |
160 |
206 |
206 |
213 |
251 |
* Units may be ordered with right hand controls, i.e. controls
access, flue and air inlet on right-hand side (non standard).
** Units
may be base mounted on a suitable non-combustible surface.
|
|