| SPECIFICATION 'T'
SERIES
Cabinets
All components exposed to products of combustion are manufactured
from aluminised steel. Exterior panels have a baked-paint finish.
Heat Exchanger
The Thermocore venturi tube heat exchanger assembly is manufactured
from special grade aluminised steel. For applications using fresh air or
where the temperature rise across the unit is less than 22oC,
optional stainless steel (AISI 409) heat exchangers are recommended.
Burners
Corrosion resistant aluminised steel burners with stainless steel
ribbons are mounted in a slide-out burner tray. The burner tray
withdraws from the left side of the unit (when facing the air
discharge), opposite hand units are available as an option.
Gas and Safety Controls
Standard 'T' series models are fitted with a multi-function gas
control valve permanent pilot and a thermoelectric safety control
system. Fully automatic electronic ignition may be fitted as an
option. An integral fan control delays the fan operation until the
unit has reached operating temperature. The fan control also allows
for fan overrun after the burners have switched off so that all
residual heat is dissipated into the building.
A limit switch thermostat shuts down
the heater in the event of overheating. For additional safety a dual
limit thermostat is fitted on all EnviroAir units.
Air Handling
TA models are fitted with direct drive axial flow fans and single
phase 230V motors. TA units are supplied complete with horizontal
louvres.
TB and TE models are fitted with double
inlet, centrifugal blowers, complete with belt drive. An adjustable
pulley is fitted to allow small variations for on-site balancing.
Standard units are fitted with single phase 230V motors, optional
three phase motors are available for increased duty.
TB and TE are supplied as standard with
a duct outlet flange for connection to ductwork. The data table
indicates the airflow and static pressure available for ducted
applications with the standard motor. For higher airflows or for
static pressures up to 400 pascals, larger motors may be specified.
The data table indicates the maximum airflows available, excluding
filter and damper resistance.
TECHNICAL DATA
| |
75 |
100 |
125 |
150 |
175 |
200 |
225 |
250 |
300 |
350 |
400 |
| NOMINAL HEAT
OUTPUT |
kW |
17 |
23 |
29 |
35 |
41 |
47 |
52 |
59 |
70 |
81 |
93 |
| GAS RATE G20 Nat Gas |
m³/h |
2.05 |
2.73 |
3.41 |
4.10 |
4.78 |
5.46 |
6.15 |
6.83 |
8.20 |
8.57 |
10.95 |
| GAS CONNECTION |
BSP in |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
¾ |
| NOMINAL FLUE DIAMETER |
mm |
125 |
150 |
175 |
200 |
200 |
200 |
200 |
200 |
250 |
250 |
250 |
| AXIAL FAN MODELS TA |
| AIRFLOW
FREEBLOWING |
m³/h |
2040 |
2040 |
2460 |
3300 |
3300 |
4260 |
4260 |
5700 |
5700 |
6600 |
7560 |
| MOTOR RATING |
kW |
0.34 |
0.34 |
0.34 |
0.34 |
0.34 |
0.47 |
0.47 |
0.58 |
0.58 |
0.82 |
0.82 |
| MOUNTING
HEIGHT |
m |
2.5 |
2.5 |
2.5-
3.0 |
2.5-
3.0 |
2.5-
3.0 |
2.5-
3.25 |
2.5-
3.25 |
2.5-
3.5 |
2.5-
3.5 |
2.5-
4.0 |
2.5-
4.0 |
| THROW * |
m |
16 |
16 |
20 |
24 |
24 |
28 |
28 |
30 |
30 |
35 |
38 |
| CENTRIFUGAL FAN MODELS TB &
TE |
| AIRFLOW
FREEBLOWING |
m³/h |
1908 |
2556 |
3384 |
3960 |
4068 |
5040 |
5616 |
6408 |
7668 |
8500 |
8856 |
| MOUNTING
HEIGHT |
m |
2.5-
3.0 |
3.0 |
3.0 |
3.0-
3.5 |
3.0-
3.5 |
3.0-
4.0 |
3.0-
4.0 |
3.0-
4.0 |
3.0-
4.5 |
3.0-
4.5 |
3.0-
5.0 |
| THROW * |
m |
18 |
24 |
25 |
31 |
31 |
31 |
32 |
32 |
34 |
35 |
47 |
| MOUNTING
HEIGHT c/w 90° |
m |
- |
3.0-
4.0 |
3.0-
5.0 |
3.0-
6.0 |
3.0-
6.0 |
3.5-
7.0 |
3.5-
7.0 |
3.5-
7.0 |
4.0-
8.0 |
4.0-
9.0 |
4.0-
10.0 |
| STANDARD MOTOR |
kW |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.56 |
0.75 |
0.75 |
1.10 |
1.10 |
1.10 |
| AIRFLOW DUCTED
(Standard Motor) |
m³/h |
1650 |
2040 |
2550 |
2900 |
3400 |
4250 |
4700 |
5100 |
5950 |
7300 |
7600 |
| MAXIMUM PRESSURE (Standard Motor) |
kW |
250 |
250 |
200 |
150 |
100 |
100 |
100 |
150 |
200 |
100 |
100 |
| MAXIMUM MOTOR
SIZE |
kW |
1.1 |
1.1 |
1.1 |
1.5 |
1.5 |
2.2 |
2.2 |
3.0 |
3.0 |
3.0 |
3.0 |
| MAXIMUM
AIRFLOW |
m³/h |
3000 |
3000 |
4000 |
5000 |
5000 |
7200 |
7200 |
9000 |
9000 |
10,500 |
10,500 |
| MAX PRESSURE AT MAXIMUM AIRFLOW |
Pa |
400 |
400 |
400 |
400 |
400 |
150 |
150 |
400 |
400 |
200 |
50 |
| MAXIMUM AIRFLOW AT 400Pa |
m³/h |
3000 |
3000 |
4000 |
5000 |
5000 |
6400 |
6400 |
9000 |
9000 |
10,000 |
11,000 |