EnviroAir
 
 
  SPECIFICATION 'T' SERIES

Cabinets
All components exposed to products of combustion are manufactured from aluminised steel. Exterior panels have a baked-paint finish.

Heat Exchanger
The Thermocore venturi tube heat exchanger assembly is manufactured from special grade aluminised steel. For applications using fresh air or where the temperature rise across the unit is less than 22
oC, optional stainless steel (AISI 409) heat exchangers are recommended.

Burners
Corrosion resistant aluminised steel burners with stainless steel ribbons are mounted in a slide-out burner tray. The burner tray withdraws from the left side of the unit (when facing the air discharge), opposite hand units are available as an option.

Gas and Safety Controls
Standard 'T' series models are fitted with a multi-function gas control valve permanent pilot and a thermoelectric safety control system. Fully automatic electronic ignition may be fitted as an option. An integral fan control delays the fan operation until the unit has reached operating temperature. The fan control also allows for fan overrun after the burners have switched off so that all residual heat is dissipated into the building.

A limit switch thermostat shuts down the heater in the event of overheating. For additional safety a dual limit thermostat is fitted on all EnviroAir units.

Air Handling
TA models are fitted with direct drive axial flow fans and single phase 230V motors. TA units are supplied complete with horizontal louvres.

TB and TE models are fitted with double inlet, centrifugal blowers, complete with belt drive. An adjustable pulley is fitted to allow small variations for on-site balancing. Standard units are fitted with single phase 230V motors, optional three phase motors are available for increased duty.

TB and TE are supplied as standard with a duct outlet flange for connection to ductwork. The data table indicates the airflow and static pressure available for ducted applications with the standard motor. For higher airflows or for static pressures up to 400 pascals, larger motors may be specified. The data table indicates the maximum airflows available, excluding filter and damper resistance.

TECHNICAL DATA

  75 100 125 150 175 200 225 250 300 350 400
NOMINAL HEAT OUTPUT kW 17 23 29 35 41 47 52 59 70 81 93
GAS RATE G20 Nat Gas m³/h 2.05 2.73 3.41 4.10 4.78 5.46 6.15 6.83 8.20 8.57 10.95
GAS CONNECTION BSP in ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾
NOMINAL FLUE DIAMETER mm 125 150 175 200 200 200 200 200 250 250 250
AXIAL FAN MODELS TA
AIRFLOW FREEBLOWING m³/h 2040 2040 2460 3300 3300 4260 4260 5700 5700 6600 7560
MOTOR RATING kW 0.34 0.34 0.34 0.34 0.34 0.47 0.47 0.58 0.58 0.82 0.82
MOUNTING HEIGHT m 2.5 2.5 2.5-
3.0
2.5-
3.0
2.5-
3.0
2.5-
3.25
2.5-
3.25
2.5-
3.5
2.5-
3.5
2.5-
4.0
2.5-
4.0
THROW * m 16 16 20 24 24 28 28 30 30 35 38
CENTRIFUGAL FAN MODELS TB & TE
AIRFLOW FREEBLOWING m³/h 1908 2556 3384 3960 4068 5040 5616 6408 7668 8500 8856
MOUNTING HEIGHT m 2.5-
3.0
3.0 3.0 3.0-
3.5
3.0-
3.5
3.0-
4.0
3.0-
4.0
3.0-
4.0
3.0-
4.5
3.0-
4.5
3.0-
5.0
THROW * m 18 24 25 31 31 31 32 32 34 35 47
MOUNTING HEIGHT c/w 90° m - 3.0-
4.0
3.0-
5.0
3.0-
6.0
3.0-
6.0
3.5-
7.0
3.5-
7.0
3.5-
7.0
4.0-
8.0
4.0-
9.0
4.0-
10.0
STANDARD MOTOR kW 0.37 0.37 0.37 0.37 0.37 0.56 0.75 0.75 1.10 1.10 1.10
AIRFLOW DUCTED (Standard Motor) m³/h 1650 2040 2550 2900 3400 4250 4700 5100 5950 7300 7600
MAXIMUM PRESSURE (Standard Motor) kW 250 250 200 150 100 100 100 150 200 100 100
MAXIMUM MOTOR SIZE kW 1.1 1.1 1.1 1.5 1.5 2.2 2.2 3.0 3.0 3.0 3.0
MAXIMUM AIRFLOW m³/h 3000 3000 4000 5000 5000 7200 7200 9000 9000 10,500 10,500
MAX PRESSURE AT MAXIMUM AIRFLOW Pa 400 400 400 400 400 150 150 400 400 200 50
MAXIMUM  AIRFLOW AT 400Pa m³/h 3000 3000 4000 5000 5000 6400 6400 9000 9000 10,000 11,000

* Throw depends on height of building, mounting height of heater, room temperature and louvre settings.

 