| 'T' and 'ST'
SERIES INSTALLATION Location For applications supplying fresh air ventilation, stainless steel heat exchangers (AISI 409) are recommended. Where chlorinated vapours or certain other contaminants may be present, special grade stainless steel (AISI 316) should be specified. Whilst the units are suitable for most industrial and commercial applications, standard units must not be installed in atmospheres containing highly flammable vapours, combustible dust, halogenated hydrocarbons or chlorinated vapours. For such applications, separated combustion units or remotely-sited units will be required, depending on the application. Care should be taken to ensure that the units are level and isolated from any vibrations. ALWAYS ENSURE ADEQUATE COMBUSTION AIR IS PROVIDED IN COMPLIANCE WITH BS5440 AND/OR BS 6230 DEPENDENT ON HEAT OUTPUT OF THE APPLIANCE.
Room sealed ST heaters are fitted with
integral power flue venters and a differential air pressure switch.
The pressure switch monitors flow and shuts down the heater in the
event of flue or combustion air blockage. To comply with CE approvals,
room-sealed ST appliances must be used with the sealed flue system
provided by the manufacturer. The balanced flue terminal provides both
the flue outlet and air inlet from a single building penetration. The
balanced flue outlets are ordered separately from the heater and a
choice of wall outlet or roof outlet is available. Up to 9 metres of
additional pipe can be added to both the flue and the combustion air
inlet (reduce by 1.5 metres for each 90o
bend). Connections to the heater flue outlet and combustion air inlet require sealed single wall pipe. Gas Supply Standard units are supplied for use on natural gas and require a minimum inlet pressure of 17.5mbar. Maximum inlet gas pressure to the unit should not exceed 30mbar. Electrical
* Varies according to roof pitch |
||||||||||||||||||||||||||||||||